Single−axis controllers
Rated data
Fuses and cable cross−sections
3
62
EDS94SPP101 EN 10.2
Operation with external mains choke/mains filter, installation according to UL
Only use UL−approved cables, fuses and fuse holders.
UL fuse: Voltage 600 V; CC, J or T class fuses
Type standard installation motor group installation FI
1)
L1, L2, L3 L1, L2, L3
[A] [AWG] [A] [AWG] [mA]
E94ASxE0024 8 16 15 14 300
E94ASxE0034 10 16 15 14 300
E94ASxE0044 15 14 20 12 300
E94ASxE0074 20 12 20 12 300
E94ASxE0134 45 8 60 6 300
E94ASxE0174 60 6 60 6 300
E94ASxE0244 60 6 60 6 300
Fuse
1)
Universal−current−sensitive earth−leakage circuit breaker, RCD type B
If several devices or cable lengths > 50 m are used, it is possible that the circuit breaker will respond, depending on
the type of cable and the switching frequency.
Observe national and regional regulations!