Single−axis controllers
Rated data
Fuses and cable cross−sections
3
63
EDS94SPP101 EN 10.2
Operation without external mains choke/mains filter, installation according to
EN 60204−1
The data are recommendations. Other dimensioning/laying systems are possible (e.g.
according VDE 0298−4).
The cable cross−sections apply under the following conditions:
ƒ Use of PVC−insulated copper cables
ƒ Conductor temperature < 70 °C, ambient temperature < 45°C
ƒ No bundling of cables or cores
ƒ Three loaded cores
Type L1, L2, L3 − laying system FI
1)
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [mA]
E94ASxE0024 C10 − 1.5 1.5 − 300
E94ASxE0034 C10 − 1.5 1.5 − 300
E94ASxE0044 C10 − 1.5 1.5 − 300
E94ASxE0074 C16 − 2.5 2.5 − 300
E94ASxE0134 C20 − 6 2.5 − 300
E94ASxE0174 C25 − 6 4 − 300
E94ASxE0244 C40 − 10 10 − 300
E94ASxE0324
2)
− 50 16 10 − 300
E94ASxE0474
2)
− 63 25 16 − 300
E94ASxE0594
2)
− 80 25 25 − 300
E94ASxE0864
2)
− 100 − 35 − 300
E94ASxE1044
2)
− 125 − 50 − 300
E94BSxE1454
2)
− 200 − − 70 300
E94BSxE1724
2)
− 250 − − 95 300
E94BSxE2024
2)
− 315 − − 150 300
E94BSxE2454
2)
− 350 − − 150 300
E94BSxE2924
2)
− 400 − − 185 300
E94BSxE3664
2)
− 500 − − 240 300
E94BSxE4604
2)
− 500 − − 2 x 150 300
Circuit breaker
Fuse of the utilisation category gG/gL or semiconductor fuses or the utilisation category gRL
1)
Universal−current−sensitive earth−leakage circuit breaker, RCD type B
If several devices or cable lengths > 50 m are used, it is possible that the circuit breaker will respond, depending on
the type of cable and the switching frequency.
2)
Device with integrated mains choke
Observe national and regional regulations!