EasyManua.ls Logo

LS Industrial Systems Metasol Series - Circuit Diagram; Condenser Trip Device (CTD); Externals and Ratings

LS Industrial Systems Metasol Series
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108
Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
I
1. Externals and Ratings
It gets a circuit breaker tripped electrically within regular
time when control power supply is broken down and is
used with Shunt coil, SHT.
In case there is no DC power, It can be used as the
rectifier which supplies DC power to a circuit breaker by
rectifying AC power.
2. Ratings 3. Circuit Diagram
Condenser Trip Device (CTD)
Ratings
Specification
CTD-100
AC 100/110
50/60
140/145
Within 5S
Over 3 MIN
85~110
400
CTD-200
AC 200/220
50/60
280/310
Within 5S
Over 2 MIN
85~111
160
Type name
Rated input voltage (V)
Frequency (Hz)
Rated charge voltage (V)
Charging time
Trip possible time
Range of Input voltage (%)
Condenser capacity
4. External Dimension
Front View Side View Rear View
AC
(INPUT)
16
35
DC
(OUTPUT)

Table of Contents