130
Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
J
Fig. 2. Transporting method of Fixed type
10
Fig. 3. Transporting method of Draw-out type
1.To lift the breaker (Fixed type), use the lifting hooks on the sides of the breaker, and lift with rope or
something similar.
2. When placing the breaker on the ground, be careful not to drop or to impact the breaker.
3. When the draw-out breaker is lifted with the cradle, lift it in the connected position.
4. Never slide the breaker when handling.
Precaution of Transporting
Fig. 4. Storage method
When storing a circuit breaker for a long term,
1. Keep the breaker at OFF position with the charging spring discharged.
2. Store the draw-out type breaker on the flat place after the TEST position inserted.
Precaution of Storage
1. Store the breaker in a dust free and dry environment.
2. Keep the breaker in OFF position with the charging spring discharged.
3. Cover the breaker with a vinyl sheet or a similar cover. When putting the breaker into service after long
term storage, it is unnecessary to lubricate the parts of the breakers.
4. Keep the breaker indoor as it was packaged around 15 and under 50% of humidity.
5. Standard packing condition for domestic portage is not suited to outdoor storage. If you cannot keep the
maintenance above, you should inspect a degree of the damages before you install the products.
6. Unsuitable keeping does not guarantee good qualities of the products and could occur additional danger
of an accident.