29
D
Digital Trip Relay
D
(0.4-0.5-0.6-0.7-0.8-0.9-1.0)ln
(0.5-1-2-4-8-12-16-20-off)lr@6lr
(1.5-2-3-4-5-6-8-10-off)lr
l
2
t off : (0.05-0.1-0.2-0.3-0.4)lr
l
2
t on : (0.1-0.2-0.3-0.4)lr
(2-3-4-6-8-10-12-15-off)ln
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-off)ln
l
2
t off : (0.05-0.1-0.2-0.3-0.4)
l
2
t on : (0.1-0.2-0.3-0.4)
(0.5-0.6-0.7-0.8-0.9-1.0)ln
(0.8-0.83-0.85-0.88-0.89-0.9-0.93-0.95-0.98-1.0)lu
(0.5-1-2-4-8-12-16-20-off)lr@6lr
(1.5-2-3-4-5-6-8-10-off)lr
l
2
t off : (0.05-0.1-0.2-0.3-0.4)lr
l
2
t on : (0.1-0.2-0.3-0.4)lr
(2-3-4-6-8-10-12-15-off)ln
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-off)ln
l
2
t off : (0.05-0.1-0.2-0.3-0.4)
l
2
t on : (0.1-0.2-0.3-0.4)
2. Externals and Configuration
N, A type Knob Information
N, A / S Type Knob Configuration
S type Knob Configuration
lu
lr
tr
ls
tsd
li
lg
tg
No
Mode
Type of Knob Setting Step
Long-time current setting
Long-time current setting
Long-time tripping delay
Short-time current Setting
Short-time tripping delay
Instantaneous pick-up
Ground-fault pick-up
Ground-fault tripping delay
lr
tr
ls
tsd
li
lg
tg
No
Mode
Type of Knob Setting Step
Long-time current setting
Long-time tripping delay
Short-time current Setting
Short-time tripping delay
Instantaneous pick-up
Ground-fault pick-up
Ground-fault tripping delay
N, A Type Knob Configuration S Type Knob Configuration


Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS Industrial Systems Metasol Series and is the answer not in the manual?

LS Industrial Systems Metasol Series Specifications

General IconGeneral
BrandLS Industrial Systems
ModelMetasol Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals