Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
D
UV, under voltage 80V ~ OV_pickup 5% 1V
OV, over voltage UV_pickup ~ 980V 5% 1V
Vunbal, Voltage Unbalance
6% ~ 99% 2.5% or *10% 1%
rP, Reverse Power 10 ~ 500kW 10% 1kW
Lunbal, Current Unbalance
6% ~ 99% 2.5% or *10% 1% 1.2 ~ 40 0.1 0.1
60Hz UF_pickup ~ 65 0.1Hz 1Hz
sec sec sec
50Hz UF_pickup ~ 55 0.1Hz 1Hz
60Hz 55Hz ~ OF_pickup 0.1Hz 1Hz
50Hz 45Hz ~ OF_pickup 0.1Hz 1Hz
OF, over
frequency
UF, under
frequency
1. UVR - Under Voltage Relay
Off/Alarm/DO is available when under voltage occurs to one of the 3 phases.
1) Pickup standard voltage setting (UV_pickup): 80 ~ OVR_PickUp
Note1
) V (Step: 1V)
2) Delay Time (tuvp): 1.2 ~ 40 sec (Step : 0.1 sec)
3) Relay error: Pickup value 5%, Operating time 0.1sec.
4) Remark: From 3P Voltage, Max. voltage operate at above 60V.
2. OVR - OVER Voltage Relay
Off/Alarm/DO is available when under voltage occurs to one of the 3 phases.
1) Pickup standard voltage setting (OV_pickup): UV_pickup
Note2
) ~ 900V (Step: 1V)
2) Pickup time delay setting (tovp): 1.2 ~ 40 sec (Step: 0.1 sec)
3) Relay error: Pickup value 5%, operating time 0.1 sec.
3. rPower - Reverse Power Protection
Off/Alarm/DO setting available when total active power of 3P flows reverse above the setting.
1) Pickup setting: 10 ~ 500kW (Step: 1kW)
2) Pickup time delay setting: 1.2 ~ 40 sec (Step: 0.1 sec)
3) relay error: Pickup value 10%, Operating time 0.1sec.
4) Calculating formula and Remark: absolute power phase angle difference
(Voltage phase difference- Current phase difference) 0 ~ 60°
Note 1) OVR_PickUp - OVR Pickup setting voltage
2) UV_PickUp - UVR Pickup setting voltage
Relay Selection Standard Table
Optional Relays for P,S Type - OV, UV, rPower
Delay
Pickup AccuracyPickup Setting Range
Operating Time Accuracy
Adj. Unit
Adj. Unit