EasyManua.ls Logo

LS Industrial Systems Metasol Series - Trip Alarm Switch, al; Electrical Characteristics of al Switch; Externals

LS Industrial Systems Metasol Series
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
C
In case a circuit breaker is tripped by OCR which operates against the faulty current (Over Current Relay),
Trip Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from
the mechanical indicator on main cover of main circuit breaker or internal auxiliary switch.
When a circuit breaker tripped by faulty current, a mechanical trip indicator (MRB, Manual Reset Button) pops out
from the main cover and the switch (AL) which sends control signal electrically is conducted to output the
information occurred from faulty circuit breaker.
MRB can be operated only by OCR but not by OFF operation of circuit breaker.
To re-close a circuit breaker after a trip, press MRB to reset it for closing.
2pcs of Electrical trip switch (AL1, AL2, 1a) are provided (OPTION)
4. Trip Alarm Switch, AL
Rated Voltage
[Vn]
Non-Inductive Load (A)
Rated Voltage
Inrush
Current
8V DC
30V DC
125V DC
250V DC
250V AC
11
10
0.6
0.3
11
3
3
0.1
0.05
1.5
6
6
0.6
0.3
6
3
3
0.1
0.05
2
MAX. 24A
Resistive Load
Lamp Load
Motor Load
Inductive Load (A)
Electrical Characteristics of AL Switch
Externals
AL2, 1a
AL1, 1a

Table of Contents

Related product manuals