56
Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
D
Overlapped Setting Possible
Relay for
signal
Classification
Contact switching capacity
Max. switching capacity
Contact switching capacity
Max. switching capacity
Remarks
Applied range
Resistance load cos =1
Induction load
(cos =0.4, L/R=7ms)
AC230V 12A / DC25V 12A
2760VA, 300W
AC230V 6A / DC25V 6A
1880VA, 150W
DO#1
DO#2
DO#3
UFROFRIunbalVunbalrPowerUVROVRGroundInst.ShortLong
Overload
Alarm
1. The use of Solid Relay
P and S type are equipped with 3 Solid Relays.
1) Terminal number is 524-534-544-513 (513 is Relay common terminal) and are contacts at Normal Open state.
2) Relay of 3 can be variously (overlapping) used by setting the environment.
Accident indication (Long/short time delay, instantaneous, ground fault, UVR, OVR, UFR, OFR, rPower,
Vunbal, Iunbal)
Closes set Relay when corresponding accident occurs.
(Maintains state as Latch form until user pushes Reset)
For overload alarm (Closes corresponding Relay at over 90%)
General purpose DO (Can remotely Close/Open the corresponding Relay)
2. Rated Output
3. Possible Relay Composition