Chapter 7. Function List
Display Name
Min/Max
range
Description
Factory
defaults
Adj.
during run
P31
Dwell
frequenc-
y
0.1 ~
200
[Hz]
When run frequency is issued, motor starts
to accelerate sfter dwell frequency is
applied to the motor during dwell
time(P32).
It can be set within max frequency(P16)
and start frequency(P18).
5.00 X
P32
Dwell
time
0~10
[sec]
Sets the time for dwell operation. 0.0 X
P33
Operator’
-s fault
detection
0 ~ 7
[bit]
Sets fault detection items at operator’s
discretion
0
O
Func.
Set
Earth
detection
during
run(GCt)
Input
phase
detection
(CoL)
Output
phase
detection
(Pot)
bit2 bit1 bit0
0 - - -
1 - -
2 -
-
3 -
4
- -
5
-
6
-
7
P34
Power
On Start
Selection
0 ~ 1
It is activated when drv is set to 1 or 2.
Motor starts acceleration after AC power is
applied while FX or RX terminal is ON.
0 X
P35
Restart
after fault
reset
selection
0 ~1
It is activated when drv is set to 1 or 2
(Run/Stop via Control terminal).
Motor accelerates after the fault condition is
reset while the FX or RX terminal is ON.
0 O