EasyManua.ls Logo

LSIS H100-2 - Page 358

LSIS H100-2
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Learning Protection Features
344
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
88
Fan replacement
alarm level
Fan
Exchange
90.0
0.0100.0
%
CNF
75
Initializing the
accumulation
time of the fan
operation
Fan Time
Rst
0: No
0
No
1
Yes
OUT
3135
Relay 15 output
Relay 15
35
Fan Exchange
-
Fan Life Estimation Setting Details
Code
Description
PRT-87 Fan Time
Perc
Displays the time the fan is used in percentage based on 50,000 hours.
If this value is bigger than the value in PRT-88, the warning
message‖Fan Exchangeappears on the display.
PRT-88 Fan
Exchange
Displays the life replacement standard of the fan in percentage.
CNF-75 Fan Time
Rst
Initializes the accumulation time of the fan operation.
Setting
Function
0
No
Do not initialize the accumulated operation time of the
fan.
1
Yes
Initialize the accumulated operation time of the fan.
Be careful when replacing the battery. Remaining voltage in the battery may cause electric
shock.
Make sure that the battery doesnt fall inside of the inverter.
Fan life examination is only for the reference and cannot be used as an absolute value.

Table of Contents

Related product manuals