Table of Functions
467
8.10 Application 1 Function Group (AP1)
Data in the following table will be displayed only when the related code has been selected.
Unit MAX = PID Unit 100%
Unit Min = (2xPID Unit 0%-PID Unit 100%)
Unit Default = (PID Unit 100%-PID Unit 0%)/2
Unit Band = Unit 100%-Unit 0%
*O/X: Write-enabled during operation,Δ: Writing available when operation stops
Cod
e
Comm.
Addres
s
Name
LCD
Display
Setting Range
Initial
Value
Property
*
Ref.
00
-
Jump Code
Jump
Code
199
20
O
p.65
05
0h1A0
5
Sleep boost
amount
Sleep
Bst Set
0.00Unit Max
0.00
O
p.17
5
06
0h1A0
6
Sleep boost
speed
Sleep
BstFreq
0.00, Low
Freq High
Freq
60.00
O
p.17
5
07
0h1A0
7
PID sleep mode 1
delay time
PID
Sleep 1
DT
0.06000.0
(sec)
20.0
O
p.17
5
08
0h1A0
8
PID sleep mode 1
frequency
PID
Sleep1Fr
eq
0.00, Low
Freq High
Freq
0.00
O
p.17
5
09
0h1A0
9
PID wakeup 1
delay time
PID
WakeUp
1 DT
0.06000.0
(sec)
20.0
O
p.17
5
10
0h1A0
A
PID wakeup 1
value
PID
WakeUp
1Dev
0.00Unit Band
20.00
O
p.17
5
11
0h1A0
B
PID sleep mode 2
delay time
PID
Sleep 2
DT
0.06000.0
(sec)
20.0
O
p.17
5
12
0h1A0
C
PID sleep mode 2
frequency
PID
Sleep2Fr
eq
0.00, Low
Freq High
Freq
0.00
O
p.17
5