Table of Functions
468
Cod
e
Comm.
Addres
s
Name
LCD
Display
Setting Range
Initial
Value
Property
*
Ref.
13
0h1A0
D
PID wakeup 2
delay time
PID
WakeUp
2 DT
0.0–6000.0
(sec)
20.0
O
p.17
5
14
0h1A0
E
PID wakeup 2
value
PID
WakeUp
2Dev
0.00–Unit Band
20.00
O
p.17
5
20
0h1A1
4
Soft Fill function
options
Soft Fill
Sel
0
No
0: No
O
p.17
4
1
Yes
21
0h1A1
5
Pre- PID
operation
frequency
Pre-PID
Freq
Low Freq– High
Freq
30.00
O
p.17
4
22
0h1A1
6
Pre- PID delay
time
Pre-PID
Delay
0.0–600.0 (sec)
60.0
O
p.17
4
23
0h1A1
7
Soft Fill escape
value
Soft Fill
Set
Unit Min–Unit
Max
20.00
O
p.17
4
24
0h1A1
8
Soft Fill reference
increasing value
Fill Step
Set
0.00–Unit Band
2.00
O
p.17
4
25
0h1A1
9
Soft Fill reference
increasing cycle
Fill Step
Time
0–9999 (sec)
20
O
p.17
4
26
0h1A1
A
Soft Fill changing
amount
Fill Fdb
Diff
0.00–Unit Band
0.00
O
p.17
4
30
0h1A1
E
Flow Comp
function options
Flow
Comp
Sel
0
No
0: No
O
p.18
9
1
Yes
31
0h1A1
F
Max Comp
amount
Max
Comp
Value
0.00–Unit Band
0.00
O
p.18
9
40
58
0h1A2
8
MMC option
selection
MMC
Sel
0
None
0: None
Δ
p.26
0
58
Set PID-1 to 'YES' to configure AP1-40.