399
RS-485 Communication Features
OUT-3135 (Relay1–5) must be set to ‗0 (none) to control outputs via communication.
7.4.5.6 MultiState Input Object Instance
Instance ID
Object Name
Description
Units
R/W
MSI1
UnitsDisplay
Displays Unit setting
1 Hz
2 RPM
R
7.4.5.7 Error Message
Display
Description
serviceserror+7
Inconsistent parameters
propertyerror+9
Invalid data type
serviceserror+10
Invalid access method
serviceserror+11
Invalid file start
serviceserror+29
Service request denied
objecterror+31
Unknown object
propertyerror+0
Property other
propertyerror+27
Read access denied
propertyerror+32
Unknown property
propertyerror+37
Value out of range
propertyerror+40
Write access denied
propertyerror+42
Invalid array index
clienterror+31
Unknown device
resourceserror+0
Resources other
clienterror+30
Time out
abortreason+4
Segmentation not supported
rejectreason+4
Invalid tag