Technical Specification
546
Three Phase 400 V (30.090.0 kW)
Model H1004
0300
0370
0450
0550
0750
0900
Applied Motor
HP
40
50
60
75
100
120
kW
30
37
45
55
75
90
Rated
output
Rated Capacity (kVA)
46.5
57.1
69.4
82.0
108.2
128.8
Rated
Current (A)
Three-Phase
61
75
91
107
142
169
Single-Phase
36
39
47
55
73
86
Output Frequency
0400 Hz
Output Voltage (V)
3-Phase 380480 V
Rated
input
Working
Voltage (V)
Three-Phase
3-Phase 380480 VAC (-15%+10%)
Single-Phase
1-Phase 480 VAC (-5%+10%)
Input
Frequency
Three-Phase
5060 Hz (5%)
Single-Phase
60 Hz(5%)
Rated Current (A)
69.1
69.3
84.6
100.1
133.6
160.0
Weight (kg)
7.5
26
35
35
43
43
The standard motor capacity is based on a standard 4-pole motor.
The standard used for 200 V inverters is based on a 220 V supply voltage, and 400 V
inverters are based on a 440 V supply voltage.
The rated output current is limited based on the carrier frequency set at CON-04.