z Power On Start select
Group Code Parameter Name Setting Range Initial Unit
Drive group
drv [Drive mode] 1, 2
0 ~ 3 1
Function group 2
H20 [Power On Start select] 1
0 ~ 1 0
Set H20 to 1.
When AC input power is applied to the inverter with drv set to 1 or 2 {Run via control
terminal} ON, motor starts acceleration.
This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485
communication}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly upon applying AC input power.
Run
command
Frequency
Input voltage
When H20 is 0 When H20 is 1
z Restart after fault reset
Group Code Parameter Name Setting Range Initial Unit
Drive group
drv [Drive mode] 1, 2
0 ~ 3 1
Function group 2
H21
[Restart after fault reset
selection]
1
0 ~ 1 0
Set H21 to 1.
Motor starts acceleration if drv is set to 1 or 2 and the selected terminal is ON when a fault
is cleared.
This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485
communication}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly after the fault is cleared.