XGB Analog edition manual
1 - 4
DC 1 ~ 5V
DC 0 ~ 5V
DC 0 ~ 10V
DC -10 ~ 10V
(Input resistance: 1 ㏁ min)
DC 4 ~ 20mA
DC 0 ~ 20mA
(Input resistance: 250 Ω)
Current input or Voltage input can be selected through the external
terminal wiring setting.
►In voltage mode, use V+ and COM terminal for the channel.
In current mode, short V+ and COM terminal and then use I+
and COM terminal.
16 bit binary data (Data : 14Bit)
1,000 ~ 5,000 (1 ~ 5V)
0 ~ 5,000 (0 ~ 5V)
0 ~ 10,000 (0 ~ 10V)
-10,000 ~ 10,000 (±10V)
4,000 ~ 20,000 (4 ~ 20㎃)
0 ~ 20,000 (0 ~ 20㎃)
0.250㎷ (1 ~ 5V)
0.3125㎷ (0 ~ 5V)
0.625㎷ (0 ~ 10V)
1.250㎷ (±10V)
1.0㎂ (4 ~ 20㎃)
1.25㎂ (0 ~ 20㎃)
±0.2% or less (When ambient temperature 25℃)
±0.3% or less (When ambient temperature 0 ~ 55℃)
Digital filter(4 ~ 64,000㎳)
Count average (2~64,000times)
Disconnection(DC 1~5V, DC 4~20㎃)
When input signal exceeds the effective range, holds the last effective
value.
When input signal exceeds the effective range, relevant flag turns on.
Photo-coupler insulation between input terminal and
PLC power (No insulation between channels)
Fixed type assignment: 64
7ea (when using XBM(C)-DxxxS type)
10ea (when using XB(E)C-DxxxH type)