will enable an automatic equalize function. Note that this 
control method is overridden when equalize is hardware 
disabled.
Microprocessor Control: The microprocessor board 
(CP2) is equipped with a variety of software features for 
float/equalize control. These features are also disabled by 
the hardware strap on the 113B. (See ECS Controller 
Options Product Manual, Select Code 167-790-109.)
These control methods may be used interchangeably. For 
example, the front panel switch may be used to initiate equalize, 
while an external timer may turn it off.
Fuse Board
Major and Minor Fuse Alarms are generated by the fuses on the 
board, as well as for plant distribution fuses, circuit breakers and 
user-selectable interfaces. 
The fuse board contains six fuses for power and sense voltage 
distribution in the controller, 12 fuses for battery sense voltage 
to the regulation leads of the rectifiers, three fuses for user 
defined low power distribution, and three spare fuse holders. 
A 12-position terminal block is also available for connection to 
external Major and Minor Fuse Alarm inputs and for connection 
to the three low power distribution fuses. See Table 4-E for 
terminal block (TB501) designations. 
There are three fuse board codes: BCB2 for -48V applications 
(Low Voltage Disconnect option), BCB5 for -48V applications, 
and BCB6 for +24V applications.