Lucent Technologies Lineage
®
2000 ECS-12U Controller J85501E-2
4 - 2 Installation and Setup Issue 3 July 1998
must be returned to the factory due to damage, reuse the crate
and packing material.
Check the contents against the shipping bill for completeness.
Assembled ECS-12U Controller (J85501E-2)
Self-tapping mounting screws (#12-24 size)
Wire ties
ECS-12U Controller product manual, Select Code
167-790-056
Controller schematic, wiring, and assembly drawings:
SD-83181-01, T-83181-30, and J85501E-2
Trim panels (not furnished with List BA)
Lockwasher (for grounding)
Default Factory
Settings
The ECS-12U controller is shipped equipped with a 113B, two
RIBs, and FAB. Default settings for the boards shipped from the
factory are listed below:
Table 4-A: Default Factory Settings for Circuit Boards
Feature
List 1 or 3
Factory Setting
List 2
Factory Setting
(1) Auto Restart, P105 on
113B
1 and 2
(Enable)
1 and 2
(Enable)
(2) BD Alarm, SW103 on
113B
51V 25.5V
(3) HV Alarm, SW102 on
113B
53V 26.25V
(4) EQ-HV Alarm, SW101
on 113B
55V 27.25V
(5) FL/EQ, P106 on 113B
1 and 2
(Disable)
1 and 2
(Disable)
(6) Ammeter Scale, SW109
and P401 or SW409
300A 300A