Issue 3 July 1998 Product Description 2 - 19
will also show the status of the Contactor. The red LVD/OPEN
LED and Form C contact closure are powered from the battery
side of the Contactor, while the yellow LVD/FAIL LED is
powered from the load side of the Contactor. If the rectifiers are
powered down and the Contactor is open, the red LVD/OPEN
LED will be illuminated, the Form C contact closure will show
the Contactor as open, and a Minor Fuse Alarm will be given
because the 113B sends all alarms when it loses power.
In battery plants without a Contactor, the red LVD/OPEN LED
will never illuminate, and the Form C contact closure will
always show the non-existent Contactor as open.
Controller
Options
A separate product manual, Lineage
®
2000 ECS Controller
Options (Select Code 167-790-109), provides additional
information on the Microprocessor Board, Datalogger Board,
and Voice Response Option.
Microprocessor
Board
The microprocessor board adds sophisticated firmware features
such as remote communications, optional voice response,
diagnostics, and statistics to the controller. The Voice Response
Option provides high-quality voice reporting of plant
information and access to plant functions from a remote
location.
Datalogger Board
The datalogger board may be used together with the
microprocessor option to provide general purpose ac and dc
voltage, current, and transducer monitoring and relay control.
Rectifier Adapter
Board
One or two Rectifier Adapter Boards (RAB) may be added to the
basic ECS-12U controller to permit non-Lineage
®
2000
rectifiers, whether manufactured by Lucent Technologies or not,
to be used in any combination in the battery plant. This permits
the user to obtain the latest technology features of the ECS
controller in a variety of battery plants. The bottom RAB is
associated with rectifiers 1-6. The upper RAB is associated with
rectifiers 7-12. See Figure 2-2 and Section 4, “Rectifier Port
Selection,” for more details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Lineage 2000 ECS-12U and is the answer not in the manual?

Lucent Technologies Lineage 2000 ECS-12U Specifications

General IconGeneral
BrandLucent Technologies
ModelLineage 2000 ECS-12U
CategoryController
LanguageEnglish