EasyManua.ls Logo

Lucent Technologies Lineage 2000 ECS-12U - Figure 4-13: Shunt Isolator Circuit

Lucent Technologies Lineage 2000 ECS-12U
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lucent Technologies Lineage
®
2000 ECS-12U Controller J85501E-2
4 - 20 Installation and Setup Issue 3 July 1998
the switch settings in Tables 4-G and 4-H. Use the following
procedure to reset R48 and R29.
1. With sensing inputs J1-4 and J1-5 either open or shorted
together, verify that the output at J1-7 and J1-8 reads 0.0X
mV (X can be from 1 to 5). If it does not, you may need to
readjust the factory settings of the offset (R48)
potentiometer.
2. Connect the sensing inputs to the shunt, observing proper
polarity (J1-4 to the most negative and J1-5 to the most
positive). Measure the shunt mV drop and calculate the
plant load with the formula: (Full Scale Shunt Amps/Full
Scale Shunt mV) x Shunt mV Reading. Adjust R29 to
obtain this reading on the plant ammeter. Verify a second
time.
Figure 4-13: Shunt Isolator Circuit
P1
847270022
Wire Set
AKC1B
J1
P1
To J716
on Backplane
Mounts
to Shunt
To TB1-1
To TB1-2
O-BK
O
V
Y
[1]
[6]
BL
W-BL
DS1
SW2
AKC1B
SER X:X
SW1
PS1PS2
DS2
OUTPUT
R29
R48
OFFSET
CALIBRATE
R45

Table of Contents