Lucent Technologies Lineage
®
 2000 ECS-12U Controller J85501E-2
Issue 3  July 1998  Installation and Setup  4 - 11
decimal position (DEC); for currents over 999A, place the 
jumper or slide switch to the no-decimal position (NO DEC).
The controller will only work with the shunt sizes listed in Table 
4-B. In battery plants with other shunt sizes, replace the shunt or 
use an AKC1B circuit pack. When the AKC1B is used, use 
Table 4-H instead of Table 4-B to configure SW109.   
Battery on
Discharge
Threshold
The voltage threshold for the BD alarms is set with DIP switch 
SW103. (See Figure 4-4.) Refer to Figure 4-5 or the label on the 
113B cover plate for the DIP switch settings for the desired 
alarm threshold. The same table of settings also appears on 
schematic drawing SD83181-01 and on the assembly drawing 
J85501E-2. The recommended threshold is approximately 1.0 
volt below the float voltage for nominal 48-volt plants or 
approximately 0.5 volt below float for nominal 24-volt plants.
Be sure to set DIP switch 6 of SW103 for the proper operating 
voltage. 
High Voltage
Shutdown
Thresholds
The controller is equipped with two separate high voltage 
shutdown thresholds. The first is used during normal float 
operation. The second threshold is used when the plant is in 
equalize mode. The float shutdown is set with DIP switch 
SW102 on the 113B. (See Figure 4-4.) The equalize shutdown is 
controlled by DIP switch SW101 on the 113B. The equalize 
shutdown level does not need to be set if equalize is hardware 
disabled (see “Equalize Enable/Disable.”) The recommended 
Table 4-B: SW109 DIP Switch Settings
Use These Switch Settings For These Plant Shunt Sizes
Shunt Full Scale Millivolts
123456 25mV 50mV 100mV
cooocc
 150A*  300A*  600A*
cooooo
 300A*  600A* not usable
ocoooo
 600A*    1200A   2400A
oococc
   1000A    2000A    4000A
ooocoo
   1300A    2600A    5200A
oocooo
   2000A    4000A    8000A
cooooo
   3000A    6000A not usable
oooooo
   4000A    8000A not usable
*Decimal point must be used in these settings.