Issue 3  July 1998  Acceptance Testing  5 - 5
not still available to maintain the load, the red BD LED 
may also light.
7. Within ten (10) seconds of rectifier shutdown, the 
controller should automatically restart all rectifiers. The 
RFA LED should extinguish and the NORM LED should 
come on.
8. Since one rectifier is adjusted high, the controller should 
issue another shutdown signal when the plant voltage 
again reaches the HV shutdown threshold. Verify that the 
rectifier shuts down again.
9. After the second shutdown, the controller should NOT 
automatically attempt to restart rectifiers.
NOTE The automatic restart function may be disabled by the user or 
installer by moving a jumper strap on the basic controller. (See 
Section 4, 
Installation, 
for this procedure.) This function 
should be disabled only for batteryless plants equipped with 
only one rectifier. In such an application, the controller loses 
power if the rectifier is shut down and, in the process, issues a 
restart. If the one rectifier shuts down again, the cycle will repeat 
since the controller will again lose power. To prevent a possible 
infinite cycle of shutdown and restart, the automatic restart 
function should be disabled for batteryless plants with only one 
rectifier.
10. With the rectifier(s) shut down, check the office alarm 
terminal blocks to verify that the following alarms are 
present:
PMNE, PMNA, and PMNV
If the BD LED is also lit, the following alarms should also 
be present on the terminal blocks:
BDE, PMJE, PMJA, and PMJV
11. Readjust the rectifier output voltage back down and restart 
any failed rectifiers manually (i.e., toggle the On/Off 
switch). Once all rectifiers are back on line, perform the 
fine adjustment of the rectifier output voltage. (Refer to the 
rectifier product manual for voltage adjustment 
procedures.)