ND30-09D 55 User's manual
4076 RW
-1440..
0..1440
[
o
/
oo
]
Alarm output 2 - lower value of the condition 2
switch of the rated input range
900
4077 RW
-1440..
0..1440
[
o
/
oo
]
Alarm output 2 - upper value of the condition 2
switch of the rated input range
1100
4078 RW 0..3600 s Alarm output 2 - condition 2 activation delay 0
4079 RW 0..3600 s Alarm output 2 - condition 2 deactivation delay 0
4080 RW 0..3600 s Alarm output 2 - condition 2 re-activation lock 0
4081 RW
0,1
Alarm output 2– condition 2 signalization 0
4082 RW reserved
4083 RW 0.1..54
Alarm output 2 - value for the condition 3 (c3)
(code as in Table 8)
38
4084 RW 0..9
Alarm output 2 - type for the condition 3:
0 – n_on, 1 – noFF, 2 – on, 3 – oFF, 4 – H_on,
5 – HoFF, 6 – 3non, 7 – 3noF, 8 – 3_on, 9 – 3_oF
0
4085 RW
-1440..
0..1440
[
o
/
oo
]
Alarm output 2 - lower value of the condition 3
switch of the rated input range
900
4086 RW
-1440..
0..1440
[
o
/
oo
]
Alarm output 2 - upper value of the condition 3
switch of the rated input range
1100
4087 RW 0..3600 s Alarm output 2 - condition 3 activation delay 0
4088 RW 0..3600 s Alarm output 2 - condition 3 deactivation delay 0
4089 RW 0..3600 s Alarm output 2 - condition 2 re-activation lock 0
4090 RW
0,1
Alarm output 2 - condition 2 signalization 0
4091 RW reserved
4092 RW 0.1..54
Continuous output 1 - output value
/code as in Tab. 8/
38
4093 RW 0..1
Continuous output 1 - type: 0 – (0...20) mA;
1 – (4…20) mA;
0
4094 RW
-1440..
0..1440
[
o
/
oo
]
Continuous output 1 - lower value of the input
range in [
o
/
oo
] of the rated input range
0
4095 RW
-1440..
0..1440
[
o
/
oo
]
Continuous output 1 - upper value of the input
range in [
o
/
oo
] of the rated input range
1000
4096 RW
-2400..
0..2400
Continuous output 1 - lower value of the current
output range (1 = 10 uA)
0
4097 RW 1..2400
Continuous output 1 - upper value of the current
output range (1 = 10uA)
2000
4098 RW 0..2
Continuous output 1 - manual switching on
0 – normal work, 1 – value set from the register
4096,
2 – value set from the register 4097
0
4099 RW reserved