ND30-09D 67 User's manual
Bit 9 – "1” – error in registers for
configuration of programmable group of
registers for readout
Bit 1 – "1” – used battery of RTC
Bit 8 – "1” – energy value error Bit 0 – reserved
Status 2 Register – (address 4416, R):
Bit 15 – "1” – condition 3 for alarm 2
signalization
Bit 14 – "1” – condition 2 for alarm 2
signalization
Bit 13 – "1” – condition 1 for alarm 2
signalization
Bit 12 – "1” – alarm 2 signalization
Bit 11 – "1” – alarm 2 condition 3
activated
Bit 10 – "1” – alarm 2 condition 2
activated
Bit 9 – "1” – alarm 2 condition 1
activated
Bit 8 – "1” – alarm 2 activated
Bit 7 – "1” – condition 3 for alarm 1
signalization
Bit 6 – "1” – condition 2 for alarm 1
signalization
Bit 5 – "1” – condition 1 for alarm 1
signalization
Bit 4 – "1” – alarm 1 signalization
Bit 3 – "1” – alarm 1 condition 3
activated
Bit 2 – "1” – alarm 1 condition 2
activated
Bit 1 – "1” – alarm 1 condition 1
activated
Bit 0 – "1” – alarm 1 activated
Status 3 Register – (address 4417, R): Files archive status
Bit 15 – Ethernet connected
Bit 14 – reserved
Bit 13 – reserved
Bit 12 – reserved
Bit 11 – "0” - waiting for the archiving
conditions to be met "1” - archiving in the
archiving group 2
Bit 10 – "0” - waiting for the archiving
conditions to be met "1” - archiving in the
archiving group 1
Bit 9 – reserved
Bit 8 – Archiving group 2 enabled
Bit 7 – Archiving group 1 enabled
Bit 6 – reserved
Bit 5 – copying of internal memory to
files archive from archiving group 2
Bit 4 – copying of internal memory to
files archive from archiving group 1
Bit 3 – Files archive space is full,
(less then 14 days at 1 sec. interval
to completely use a the files archive
space)
Bit 2 – 70% of files archive space is
full
Bit 1 – Files archive initialized
correctly
Bit 0 – Files archive file system error