ND30-09D 68 User's manual
Status 4 Register – (address 4418, R) reactive power characteristics:
Bit 15 – measurement with phase L3
synchronization
Bit 14 – measurement with phase L2
synchronization
Bit 13 – measurement with phase L1
synchronization
Bit 12 – measurement with current
synchronization
Bit 11 – "1” – capacity 3L max.
Bit 10 – "1” – capacity 3L min.
Bit 9 – "1” – capacity 3L
Bit 8 – "1” – leading L3 max.
Bit 7 – "1” – capacity L3 min.
Bit 6 – "1” – capacity L3
Bit 5 – "1” – capacity L2 max.
Bit 4 – "1” – capacity L2 min.
Bit 3 – "1” – capacity L2
Bit 2 – "1” – capacity L1 max.
Bit 1 – "1” – capacity L1 min.
Bit 0 – "1” – capacity L1
Status 5 Register – (address 4419, R)
Bit 8 – "1” – alarm 1 condition 3 for phase L3 active
Bit 7 – "1” – alarm 1 condition 3 for phase L2 active
Bit 6 – "1” – alarm 1 condition 3 for phase L1 active
Bit 5 – "1” – alarm 1 condition 2 for phase L3 active
Bit 4 – "1” – alarm 1 condition 2 for phase L2 active
Bit 3 – "1” – alarm 1 condition 2 for phase L1 active
Bit 2 – "1” – alarm 1 condition 1 for phase L3 active
Bit 1 – "1” – alarm 1 condition 1 for phase L2 active
Bit 0 – "1” – alarm 1 condition 1 for phase L1 active
Status 6 Register – (address 4420, R)
Bit 8 – "1” – alarm 2 condition 3 for phase L3 active
Bit 7 – "1” – alarm 2 condition 3 for phase L2 active
Bit 6 – "1” – alarm 2 condition 3 for phase L1 active
Bit 5 – "1” – alarm 2 condition 2 for phase L3 active
Bit 4 – "1” – alarm 2 condition 2 for phase L2 active
Bit 3 – "1” – alarm 2 condition 2 for phase L1 active
Bit 2 – "1” – alarm 2 condition 1 for phase L3 active
Bit 1 – "1” – alarm 2 condition 1 for phase L2 active
Bit 0 – "1” – alarm 2 condition 1 for phase L1 active