26
Control unit MGCplus
Digital inputs, digital outputs and relay outputs
4.2 Digital outputs and relay outputs
By parameterising the outputs, you assign certain functions to the outputs. For
example, if you parameterise the "Buzzer (static)" function for output NO2, you
must connect an acoustic signal transmitter to this output.
If the function is marked with "|", the output is inverted (Fail Safe).
The following functions are assigned to the outputs as default settings.
Clamp Description Function
DO1 Digital output 1 GED 2 red
DO2 Digital output 2 GED 2 green
DO3 Digital output 3 GED 1 red
DO4 Digital output 4 GED 1 green
NO1 Relay output 1 Random hit
NO2 Relay output 2 Buzzer (static)
NO3 Relay output 3 Fraud
NO4/NC4 Relay output 4 Hold-open time D1
NO5/NC6 Relay output 5 Hold-open time D2
NO6/NC6 Relay output 6 Wings closed
Table 13: Factory settings Digital outputs and Relay outputs
Function Description
ā Outputs that you assign this function "ā" to are deactivated.
Error When the control unit detects an "Error", the output is set with this func-
tion.
| Error As long as the control unit detects neither a "safety-relevant error" nor an
"error", the output is set with this function.
Wings closed Both wings are in closed position.
Wings opened Both wings are open either in direction 1 or in direction 2.
Wings opened D1 Both wings are currently opened in direction 1.
Wings opened D2 Both wings are currently opened in direction 2.
Wings locked Both wings are currently locked mechanically. You cannot move the wings by
hand.
Random hit Hits of the random check function
The random check function generated a hit. You can connect a signal lamp or
a buzzer to this output, for example.
The passage remains blocked until the random hit or validation is confirmed
with a 0 V pulse at the "random check function" input.