DKR Drive Controllers Mounting and installation 10-5
DOK-DIAX03-DKR********-PR02-EN-P
Conversion to cooling with duct
Note: If you want to make use of the possibility “Cooling with duct”,
there mustn’t be any vents near the controller heatsink in the
mounting panel of the control cabinet.
For the conversion to “Cooling with duct” please proceed as follows:
1. Remove the round cover (1) on the right side of the device.
2. Remove the cover of the heatsink (2) (on the bottom side of the
device). (The screws are accessible from below.)
3. Mount the duct cooling accessories (3) according to the instructions
supplied together with the accessories.
USchDKR4
1
2
3
H1
X4
X2
U5
U2
S2
U
4
U1
U3
H2
S1
X3X3
X9
1
6
1
7
X8
X7
1
1
0
1
1
1
DIAX03 DK
R04
Fig. 10-4: Conversion to cooling with duct (DKR04)