8 DESCRIPTION OF TERMINAL BLOCKS
+BATT/Ground Battery backup connector. In the original metal box it is possible to place a
1,2Ah/12V battery. Red fasten connector is for positive and black fasten connector is for negative
voltage battery supply.
+13,8V/Ground Power Supply connector - On the left side is positive voltage (+ 12 VDC to
+15VDC) and the right site is GND voltage.
Input 1 Alarm input 1 - It can be N.O. (normal open) to GND or +12V DC, N.C. (normal close)
to GND or +12V DC.
Input 2 Alarm input 2 - It can be N.O. (normal open) to GND or +12V DC, N.C. (normal close)
to GND or +12V DC.
Input 3 Alarm input 3 - It can be N.O. (normal open) to GND or +12V DC, N.C. (normal close)
to GND or +12V DC.
Input 4 Alarm input 4 - It can be N.O. (normal open) to GND or +12V DC, N.C. (normal close)
to GND or +12V DC.
ON/OFF System arm/disarm - It can be N.O. (normal open) to GND or +12V DC, N.C. (normal
close) to GND or +12V DC.
NOTE
Output 1 First diagnostic, remote control or alarm output. It is Open Collector output with
maximum loading current of 500mA.
Output 2 Second diagnostic, remote control or alarm output. It is Open Collector output with
maximum loading current of 500mA.
Output 3 Third diagnostic, remote control or alarm output. It is Open Collector output with
maximum loading current of 500mA.
Output 4 Fourth diagnostic, remote control or alarm output. It is Open Collector output with
maximum loading current of 500mA.