INSTALLATION MANUAL
20
AR parameter defines the maximum number of alarms trigged in IT time
IB IB parameter defines how long (in seconds) sending of alarm events is blocked when
automatic input block system in enabled.
Table of parameters:
Name
Comment
IT1
Time interval 1
st
input
IT2
Time interval 2
nd
input
IT3
Time interval 3
rd
input
IT4
Time interval 4
th
input
AR1
Maximum allowed number of events on 1
st
input
AR2
Maximum allowed number of events on 2
nd
input
AR3
Maximum allowed number of events on 3
rd
input
AR4
Maximum allowed number of events on 4
th
input
IB1
System block time on 1
st
input
IB2
System block time on 2
nd
input
IB3
System block time on 3
rd
input
IB4
System block time on 4
th
input
Table 19: IT, AR and IB parameters
Example:
Input 1 will be blocked for 10 minutes if 10 alarm events are triggered within 125 seconds
Input 2 will be blocked for 1 hour if 5 alarm events are triggered within 12 minutes.
Direct programming on the SIM card
ZEUS4-VD PROGRAMMING TABLE
SIM CARD PHONE BOOK
Name
Number
Description
IT1
125
Time interval on input 1
AR1
10
Max number of alarm events on input 1
IB1
600
System block time on input 1
IT2
720
Time interval on input 2
AR2
5
Max number of alarm events on input 2
IB2
3600
System block time on input 2
Table 20: IT, AR and IB parameters example
Remote programming by SMS
;IT1=125;AR1=10;IB1=600; IT2=720;AR2=5;IB2=3600;