19
11.2.8 OD parameters
OD parameters are used to link alarm events directly to output. OD1 to OD4 are used to link input
events to output, other are used for internal function notification.
Table of parameters:
Input 1 direct link to output
Input 2 direct link to output
Input 3 direct link to output
Input 4 direct link to output
Table 17: OD parameters
Example:
Direct programming on the SIM card
ZEUS4-VD PROGRAMMING TABLE
Alarm on IN1 trigger output 1
No direct connection between input2 and output
GSM network failure on output 2
System tamper on output 4
System ON/OFF on output 3
Table 18: OD parameters example
Remote programming by SMS
;OD1=1;OD2=0;OD6=2;OD7=4;OD8=3;
11.2.9 IT, AR and IB parameters
With these parameters user define the number of alarm events that can be triggered in chosen
interval before the systems goes in bypass mode (blocks sending alarm events to telephone
numbers).
IT – parameter defines the interval (in seconds) in which maximum AR number of alarm can be
triggered.