40
PT100 / PT1000 Inputs
Note: RTD inputs works only as pair (A0A1, B0B1, …). If A0 for example is to be used and A1
not, then A1 need to wire bridged.
Function: Reading a resistance/ temperature value (v1.0.8 and older)
/sys/sensor_carrier_board/rtd/rtd0/value
/sys/sensor_carrier_board/rtd/rtd1/value
/sys/sensor_carrier_board/rtd/rtd2/value
/sys/sensor_carrier_board/rtd/rtd3/value
/sys/sensor_carrier_board/rtd/rtd4/value
/sys/sensor_carrier_board/rtd/rtd5/value
/sys/sensor_carrier_board/rtd/rtd6/value
/sys/sensor_carrier_board/rtd/rtd7/value
/sys/sensor_carrier_board/rtd/rtd8/value
/sys/sensor_carrier_board/rtd/rtd9/value
/sys/sensor_carrier_board/rtd/rtd10/value
/sys/sensor_carrier_board/rtd/rtd11/value
/sys/sensor_carrier_board/rtd/rtd12/value
/sys/sensor_carrier_board/rtd/rtd13/value
/sys/sensor_carrier_board/rtd/rtd14/value
/sys/sensor_carrier_board/rtd/rtd15/value
Example: Read the value at RTD A0
Command: cat /sys/sensor_carrier_board/rtd/rtd0/value
Conversion at port of a resistor in Ohm
Formula: Resistance in Ohm = Value / 100
Example: Value = 100000 corresponds 1000Ohm
Conversion at port of a PT1000 temperature sensor to °Celsius
Formula: Temperature in Grad Celsius = (Value / 100 -1000) / 3,891
Example: Value = 112000 corresponds to +30,84°Celsius
Value = 100000 corresponds to 0°Celsius
Value = 90000 corresponds to -25,5°Celsius