SIA-DC09 server parameters details
To add a new SIA-DC09 server, follow the steps described on the previous section “How to add a server”,
and choose “SIA-DC09” in the protocol selector.
SIA-DC09 selection
A new page with a list of parameter should appear:
SIA-DC09 parameters
Here is the detail of the parameters needed for SIA-DC09 protocol:
Listening port:
Define the server listening port.
Panel Timeout:
Define the default value for panel timeout. This value is in seconds.
If a panel doesn’t send anything during a time superior than the set value, then a timeout event will be
send to the user.
Maximum Connections:
Maximum simultaneous connections allowed for this server. The default is 100.
If you network problem or panel timeout occurs, then you should adjust this value.
Use TCP:
By default, SIA-DC09 serve use the UDP protocol. You can use the TCP instead