DET2/3
17
Earth / ground resistivity
Earth / ground resistivity
Test procedure
Setup test
1 Connect pins / stakes
C1
CAT IV 300V
P1
P2
C2
E
ES
S
H
I
V
E
X
Y
V
MVC1010 MVC1010
MCC1010
I
C1 (E)
P1 (ES) C2 (H)P2 (S)
a a a
Wenner
or
C1
CAT IV 300V
P1
P2
C2
E
ES
S
H
I
V
E
X
Y
V
MVC1010 MVC1010
MCC1010
I
C1 (E)
P1 (ES) C2 (H)P2 (S)
a ab
Schlumberger
Note: Set up the test leads and stakes as required by the selected test method (on screen).
Do not connect the test leads to the instrument.
2 Set function to ρ
4P
4P
3P
3P
2P
A
3
Set the mode
Manual or Continuous
(see Test modes (page 11).
MAN
OFF
4 Select test method
a(a+b)R
b
2 aR
Wenner or Schlumberger
Adjust parameters
Set test measurements
Metres or Feet