DET2/3
39
Specifications
Specifications
Only values with tolerance or limits are guaranteed data. Parameters without tolerances are for information only.
Measurement specifications
2, 3 and 4 terminal resistance
Range 0.001 Ω to 20.00 kΩ Auto range
Accuracy
3P
2P
at 23 °C ±0.5% of reading ±2 digits
±10 mΩ
±20 mΩ
Operational uncertainty ±2% of reading ±2 digits
Meets IEC61557 operational uncertainty requirement with readings over 10 mΩ
when spike resistances are below 100 Ω
±5% of reading ±2 digits ±10 mΩ
Meets IEC61557 operational uncertainty requirement with readings over 50 mΩ
4 and 3 terminal ART (selective) resistance
Range 0.01 Ω to 10.00 kΩ auto range
Accuracy ±5% accuracy (±3 digits) at 23°C ±2°C
Stakeless resistance
Range 0.01 Ω to 200 Ω
Accuracy ±7% (±3 digits)
Test to standards BS 7430 (Earthing)
BS 62305 (Lightning)
IEEE Standard 81
Test frequency 2P, 3P & 4P
resistivity
10 Hz to 200 Hz (steps of 0.5 Hz)
Test frequency dual clamp,
3p ART & 4P ART
70 Hz to 200 Hz (steps of 0.5 Hz)
Test current 50 mA max.
Maximum output voltage 50 V rms
Maximum interference 50 V peak to peak
Continuity
Range 0.01 Ω to 1 kΩ (3 digits)
Accuracy ±3% (±2 digits)
Test Current Up to 205 mA
Lead Null < 10 Ω
Leakage current
Range 0.00 A to 2.00 A at 5% (+3 digits)
Accuracy ±5% (±3 digits)
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com