DET2/3
22
Leakage Current Test
Leakage Current Test
Test procedure
1 Connect MCC1010
2 Set function to A
4P
4P
3P
3P
2P
A
3 Set the mode
MAN
OFF
4 Place MCC1010 around
conductor to be tested
C1
CAT IV 300V
P1
P2
C2
E
ES
S
H
I
V
E
X
Y
V
MVC1010 MVC1010
MCC1010
I
Start Test
Manual mode
Continuous graphical mode
5
Press to start
TEST
Press
TEST
End Test
Note:
Clear: Stop the current data stream and restart the graph.
Average: Activate / deactivate the average display.
6
Press to stop
TEST
Press
TEST
7
8
Press
Press
See Data management (page 33).
OR