E-EL4 EXT
4 way 230V Extension
Leads
3 Core
Visual Inspection
Polarity
Earth Bond at 25A (x4)
Insulation test at 500V
≤0.1Ω
≥1MΩ
5s
5s PAT450
E-EL4B EXT
4 way 230V Extension
Leads
3 Core
200mA Continuity Test
Visual Inspection
Polarity
Earth Continuity (x4)
Insulation test at 500V
≤0.1Ω
≥1MΩ
5s
5s
PAT410
PAT450
E-RCD 1 Portable RCD 30mA
Visual Inspection
RCD 30mA test
PAT410
PAT450
E-RCD FULL 1 Portable RCD (5 tests)
Visual Inspection
RCD full test sequence
PAT410
PAT450
E-PSC1 1
Portable or hand-held
Class 1 equipment
Visual Inspection
Earth Continuity
Insulation test at 500V
Operation test (230V)
Differential Earth Leakage (230V)
≤0.1Ω
≥1MΩ
≤3000VA
≤0.75mA
5s
5s
5s
5s
PAT410
PAT450