45
Interpreting test results
String summary (for a string of 12 V jars)
The test results in the STRING SUMMARY (STRING STATISTICS on the printout) are averages for
the jar posts and straps in the string. If you tested without a reference value, dashes appear in the
elds that are marked in this example with asterisks (
*
).
STRING ID
ABC TEST
TECHNICIAN:
ABC123
BATTERY MANUFACTURE:
XYZ STATIONARY BATTERY
BATTERY MODEL:
MODEL 12345
9/28/2005
3:35 PM
STRING STATISTICS
* REFERENCE : 1000S
mhos (siemens) value selected in BATTERY SETUP
JARS : 4 Number of jars in the string
JARS TESTED : 4 Number of jars tested
* AVERAGE MHOS : 775S
Average conductance mhos/siemens for the string
* AVERAGE % : 77% Percentage of the reference value for the string
* DECISION : GOOD GOOD, WARN (?), or FAIL (!)
* LOW JAR : J4 50% Percentage of the reference value for the jar (J4 = fourth jar
tested) with the lowest conductance value.
* HIGH JAR : J1 90% Percentage of the reference value for the jar with the highest
conductance value. (J1 = rst jar tested)
* STRING % J1 86% The string’s average compared to the highest jar (i.e., the string’s
775 avg. mhos divided by the measured 900 mhos of highest jar.
TEMPERATURE : 72 °C Temperature selected in BATTERY SETUP
AVG. VOLTAGE : 13.917V Avg. voltage of the string.
VOLTS PER JAR : 12V Number of volts per jar selected in BATTERY SETUP
STRING WARN % (?) : 70%
STRING FAIL % (!) : 60%
JAR WARN % (?) : 70%
JAR FAIL % (!) : 60%
LOW VOLTAGE: 12.600V Low voltage threshold selected in BATTERY SETUP for the string.
DC FLOAT V. : 53.50V String oat voltage
DC FLOAT A. : 0.047A String oat current (amps)
AC RIPPLE : 0.059V String AC ripple voltage
Percentages of the reference value selected in UTILITIES
SETUP below which the string and jars must fall to generate
WARN (?) and FAIL (!) notices
on display only
on printout only
Chapter 7: Test results and reportsCelltron ULTRA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midtronics CTU-6000 and is the answer not in the manual?

Midtronics CTU-6000 Specifications

General IconGeneral
BrandMidtronics
ModelCTU-6000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals