3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 25
3.4.4 Buffer memory address comparison
Sequence program change is required as the assignment of buffer memory differs.
For details of the buffer memories and sequence program, refer to the Digital-Analog Converter Module
User's Manual.
A62DA Q62DAN
Address
(decimal)
Name Read/write
Address
(decimal)
Name Read/write
0 CH1 Digital value
R/W
0 D/A conversion enable/disable
R/W
1 CH2 Digital value 1 CH1 Digital value
2 CH1 Voltage setting value check code 2 CH2 Digital value
3 CH2 Voltage setting value check code 3
System area (Not used) -
4 CH1 Current setting value check code 4
5 CH2 Current setting value check code 5
to
10
11 CH1 Setting value check code
R
12 CH2 Setting value check code
13
System area (Not used) -
to
18
19 Error code
R
20 Setting range (CH1 to CH2)
21 System area (Not used) -
22
Offset/gain setting mode
Offset specification
R/W
23
Offset/gain setting mode
Gain specification
24 Offset/gain adjusted value specification
25
System area (Not used) -
to
157
158
Mode switching setting R/W
159
160
System area (Not used) -
to
199
200 Pass data classification setting R/W
201 System area (Not used) -
202 CH1 Industrial shipment settings offset value
R/W
203 CH1 Industrial shipment settings gain value
204 CH2 Industrial shipment settings offset value
205 CH2 Industrial shipment settings gain value
206 CH1 User range settings offset value
207 CH1 User range settings gain value
208 CH2 User range settings offset value
209 CH2 User range settings gain value