3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 1
3
3
ANALOG OUTPUT MODULE
REPLACEMENT
3.1 List of Analog Output Module Alternative Models for Replacement
Production discontinuation Transition to Q series
Product Model Model Remarks (Restrictions)
Analog output module
A616DAI Q68DAIN
1) External wiring : Cable size is changed.
2) Number of slots : Changed (2 modules are required.)
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change: 8CH/module
5) Functional specifications: Not changed
A616DAV Q68DAVN
1) External wiring : Cable size is changed.
2) Number of slots : Changed (2 modules are required.)
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change: 8CH/module
5) Functional specifications: Not changed
A62DA
Q62DAN
1) External wiring : Cable size is changed.
2) Number of slots : Not changed
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change:
Output current (minus current not applicable), I/O
characteristics
5) Functional specifications: Not changed
Q64DAN
1) External wiring : Cable size is changed.
2) Number of slots : Not changed
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change:
Output current (minus current not applicable), I/O
characteristics
5) Functional specifications: Not changed
A62DA-S1
Q62DAN
1) External wiring : Cable size is changed.
2) Number of slots : Not changed
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change: Not changed
5) Functional specifications: Not changed
Q64DAN
1) External wiring : Cable size is changed.
2) Number of slots : Not changed
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change: 4CH/module
5) Functional specifications: Not changed
A68DAI-S1 Q68DAIN
1) External wiring : Cable size is changed.
2) Number of slots : Not changed
3) Program : The number of occupied I/O points, I/O signals, and buffer
memory addresses are changed.
4) Performance specifications change:
Increase in current consumption
5) Functional specifications: Not changed