EasyManua.ls Logo

Mitsubishi Electric MELSEC-A/QnA Series - Chapter 5 Multiplexer Replacement; A60 Mx; Performance Comparison

Mitsubishi Electric MELSEC-A/QnA Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 MULTIPLEXER REPLACEMENT
5 - 1
The multiplexer module is designed especially for channel extension of the analog-digital converter
module A616AD.
Analog input signals (voltage/current) taken by the multiplexer module are output as analog output
signals (voltage) to the A616AD.
For this reason, the I/O characteristics and the maximum resolution of the multiplexer module are
adjusted to be the same as the voltage input specifications of the A616AD.
Check the set range in each channel of the existing multiplexer module to estimate the I/O
characteristics and the maximum resolution.
As regarding A60MX non-isolated multiplexer module, consider replacement using multiple Q68ADV/I.
5.1.1 Performance comparison
5
5
MULTIPLEXER REPLACEMENT
5.1 A60MX
Item A60MX
Analog input
Voltage -10 to 0 to +10VDC (Input resistance value: 1M)
Current -20 to 0 to +20mADC (Input resistance value: 250)
Analog output voltage -10 to 0 to +10VDC
I/O characteristics
Analog input range
Analog output voltage (V)
*1
Voltage (V) Current (mA)
0 to +10 0 to +20
0 to +10
0 to + 5 0 to +20
+ 1 to + 5 + 4 to +20
-10 to +10 -20 to +20
- 5 to + 5 -20 to +20
0 to +10 0 to +20
0 to + 5
0 to + 5 0 to +20
+ 1 to + 5 + 4 to +20 + 1 to + 5
-10 to +10 -20 to +20
-10 to +10
- 5 to + 5 -20 to +20
-10 to +10 -20 to +20
- 5 to + 5
- 5 to + 5 -20 to +20