3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 9
3.2.4 Buffer memory address comparison
Sequence program change is required as the assignment of buffer memories differs.
For details of the buffer memories and sequence program, refer to the Digital-Analog Converter Module
User's Manual.
A616DAI Q68DAIN
Address
(decimal)
Name Read/write
Address
(decimal)
Name Read/write
0 D/A conversion enable/disable channel
R/W
0 D/A conversion enable/disable
R/W
1 Analog output enable/disable channel 1 CH1 Digital value
2
System area (Not used) -
2 CH2 Digital value
3 3 CH3 Digital value
4 4 CH4 Digital value
5 5 CH5 Digital value
6 6 CH6 Digital value
7 7 CH7 Digital value
8 8 CH8 Digital value
9 9
System area (Not used) -
10 10
11 11 CH1 Setting value check code
R
12 12 CH2 Setting value check code
13 13 CH3 Setting value check code
14 14 CH4 Setting value check code
15 15 CH5 Setting value check code
16 CH0 Digital value
R/W
16 CH6 Setting value check code
17 CH1 Digital value 17 CH7 Setting value check code
18 CH2 Digital value 18 CH8 Setting value check code
19 CH3 Digital value 19 Error code
20 CH4 Digital value 20 Setting range (CH1 to CH4)
21 CH5 Digital value 21 Setting range (CH5 to CH8)
22 CH6 Digital value 22
Offset/gain setting mode
Offset specification
R/W
23 CH7 Digital value 23
Offset/gain setting mode
Gain specification
24 CH8 Digital value 24 Offset/gain adjusted value specification
25 CH9 Digital value 25
System area (Not used) -
26 CHA Digital value 26
27 CHB Digital value 27
28 CHC Digital value 28
29 CHD Digital value 29
30 CHE Digital value 30
31 CHF Digital value 31
32
System area (Not used) -
32
to to
47 47