3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 36
: Compatible, : Partial change required, ×: Incompatible
Q62DAN Compatibility Precautions for replacement
16-bit signed binary
Normal resolution mode: -4096 to 4095,
High resolution mode: -12288 to 12287, -16384 to 16383
Voltage: -10 to 10VDC (External load resistance value: 1k to 1M)
Current: 0 to 20mADC (External load resistance value: 0 to 600)
Ambient temperature 25±5°C: within ±0.1%
(voltage: ±10mV, current: ±20µA)
Ambient temperature 0 to 55°C: within ±0.3%
(voltage: ±30mV, current: ±60µA)
80µs/channel
Voltage: ±12V
Current: 21mA
2 channels/module
Max. 100,000 times
Available
Analog output range
Normal resolution
mode
-4000 to
4000
0 to 5V
1 to 5V
Maximum
resolution
Digital input
value
Voltage
Current
High resolution
mode
-12000 to
12000
Maximum
resolution
Digital input
value
-16000 to
16000
-12000 to
12000
0 to
12000
0 to
12000
0 to
4000
-4000 to
4000
0 to
4000
User range
settings
1.5 A
1.25mV
1.0mV
2.5mV
0.75mV
5 A
4 A
4 to 20mA
0.83 A
0 to 20mA
User range
settings
-10 to 10V
0.416mV
0.333mV
0.625mV
0.333mV
1.66 A
1.33 A

Table of Contents