EasyManua.ls Logo

Mitsubishi Electric MELSEC-A/QnA Series - Page 131

Mitsubishi Electric MELSEC-A/QnA Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 54
: Compatible, : Partial change required, ×: Incompatible
Q68DAIN Compatibility Precautions for replacement
Max. 100,000 times
Available
Between the I/O terminal and programmable controller power supply:
photocoupler isolation
Between output channels: non-isolation
Between external power supply and analog output: transformer isolation
Between the I/O terminal and programmable controller power supply:
500VAC, for 1 minute
Between the I/O terminal and programmable controller power supply:
500VDC, 20M or more
16 points
(I/O assignment: intelligent 16 points)
The number of occupied I/O points
has changed to 16 points.
18-point terminal block ×
Wiring change is required.
0.3 to 0.75mm
2
×
FG terminal: R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A
Terminals other than FG: R1.25-3
(Sleeved solderless terminal cannot be used.)
×
0.38A
The recalculation of internal current
consumption (5VDC) is required.
24VDC +20%, -15%
Ripple, spike 500mVp-p or less
0.27A
2.5A, 230µs or less -
0.20kg

Table of Contents

Related product manuals