4 TEMPERATURE INPUT MODULE REPLACEMENT
4 - 6
Q64TD
JIS Specifications
B
Measured temperature
range [°C]
0 to 600 600 to 800 800 to 1700
1700 to
1820
Conversion accuracy at
25±0.5°C [°C]
-
±3.0 ±2.5
-
Temperature characteristics
[°C]
±0.4 ±0.4
R
Measured temperature
range [°C]
-50 to 0 0 to 300 300 to 1600
1600 to
1760
Conversion accuracy at
25±0.5°C [°C]
-
±2.5 ±2.0
-
Temperature characteristics
[°C]
±0.4 ±0.3
S
Measured temperature
range [°C]
-50 to 0 0 to 300 300 to 1600
1600 to
1760
Conversion accuracy at
25±0.5°C [°C]
-
±2.5 ±2.0
-
Temperature characteristics
[°C]
±0.4 ±0.3
K
Measured temperature
range [°C]
-270 to -200 -200 to 0 0 to 1200
1200 to
1370
Conversion accuracy at
25±0.5°C [°C]
-
Larger value of ±0.5°C, or ±0.5%
of measured temperature
Larger value of ±0.5°C, or
±0.25% of measured temperature
-
Temperature characteristics
[°C]
Larger value of ±0.06°C, or
±0.2% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
E
Measured temperature
range [°C]
-270 to -200 -200 to 0 0 to 900 900 to 1000
Conversion accuracy at
25±0.5°C [°C]
-
Larger value of ±0.5°C, or ±0.5%
of measured temperature
Larger value of ±0.5°C, or
±0.25% of measured temperature
-
Temperature characteristics
[°C]
Larger value of ±0.06°C, or
±0.15% of measured
temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
J
Measured temperature
range [°C]
-210 to -40 -40 to 750 750 to 1200 -
Conversion accuracy at
25±0.5°C [°C]
-
Larger value of ±0.5°C, or
±0.25% of measured
temperature
- -
Temperature characteristics
[°C]
-
Larger value of ±0.06°C, or
±0.02% of measured
temperature
- -
T
Measured temperature
range [°C]
-270 to -200 -200 to 0 0 to 350 350 to 400
Conversion accuracy at
25±0.5°C [°C]
-
Larger value of ±0.5°C, or ±0.5%
of measured temperature
Larger value of ±0.5°C, or
±0.25% of measured temperature
-
Temperature characteristics
[°C]
-
Larger value of ±0.06°C, or
±0.1% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
-
N
Measured temperature
range [°C]
-270 to -200 -200 to 0 0 to 1250
1250 to
1300
Conversion accuracy at
25±0.5°C [°C]
-
Larger value of ±0.5°C, or ±0.5%
of measured temperature
Larger value of ±0.5°C, or
±0.25% of measured temperature
-
Temperature characteristics
[°C]
-
Larger value of ±0.06°C, or
±0.2% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
-