2 ANALOG INPUT MODULE REPLACEMENT
2 - 14
: Compatible, : Partial change required, ×: Incompatible
Q68ADV Q68ADI Compatibility Precautions for replacement
8 channels/module
Max. 100,000 times
Between the I/O terminal and programmable controller power supply:
photocoupler isolation
Between channels: non-isolated
Between the I/O terminal and programmable controller power supply:
500VAC, for 1 minute
Between the I/O terminal and programmable controller power supply:
500VDC, 20M or more
16 points
(I/O assignment: intelligent 16 points)
I/O occupied points has changed to
16 points.
18-point terminal block ×
Wiring change is required.
0.3 to 0.75mm
2
×
R1.25-3 (A solderless terminal with sleeve can not be used.) ×
0.64A 0.64A
The recalculation of internal current
consumption [5VDC] is required.
0.19kg 0.19kg