2  ANALOG INPUT MODULE REPLACEMENT
2 - 21
Item A68AD
Analog input points 8 channels/module
Maximum number of writes for 
E
2
PROM
-
Isolation method
Between the input terminal and programmable controller power supply: photocoupler isolation
Between channels: non-isolated
Dielectric withstand voltage -
Insulation resistance -
Occupied I/O points
32 points 
(I/O assignment: special 32 points)
Connected terminal 38-point terminal block
Applicable wire size
0.75 to 2mm
2
 
(Applicable tightening torque: 39 to 59N•cm)
Applicable solderless terminal V1.25-3, V1.25-YS3A, V2-S3, V2-YS3A
Internal current consumption 
(5VDC)
Hardware version K or later: 0.39A
Hardware version J or earlier: 0.9A
Weight
Hardware version K or later: 0.3kg
Hardware version J or earlier: 0.6kg