2 ANALOG INPUT MODULE REPLACEMENT
2 - 38
: Compatible, : Partial change required, ×: Incompatible
Q68AD-G Compatibility Precautions for replacement
10ms/channel
(Sampling cycle)
The conversion speed of Q68AD-G to
A68AD has become slow. If fast
conversion speed is required for
control, the Q64AD is recommended.
20ms
Voltage: ±15V
current: ±30mA
8 channels/module
Up to 50,000 times
Between the I/O terminal and programmable controller power supply:
transformer isolation
Between channels: transformer isolation
Between the I/O terminal and programmable controller power supply:
500VACrms, for 1 minute
Between analog input channels: 1000VACrms, for 1 minute
Between the I/O terminal and programmable controller power supply:
500VDC, 10M or more
Between analog input channels: 500VDC, 10M or more
16 points
(I/O assignment: intelligent 16 points)
I/O occupied points has changed to
16 points.
40-pin connector ×
Wiring change is required.
Within 0.3mm
2
×
-×
0.46A
The recalculation of internal current
consumption [5VDC] is required.
0.16kg