EasyManua.ls Logo

Mitsubishi Electric MELSEC-A/QnA Series - Page 82

Mitsubishi Electric MELSEC-A/QnA Series
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 ANALOG OUTPUT MODULE REPLACEMENT
3 - 5
Item A616DAI
Isolation method
Between the output terminal and programmable controller power supply: photocoupler isolation
A616DAI channels: non-isolation
Dielectric withstand voltage -
Insulation resistance -
Number of occupied I/O points
32 points
(I/O assignment: special 32 points)
Connected terminal 38-point terminal block
Applicable wire size
0.75 to 2mm
2
Applicable solderless terminal V1.25-3, V1.25-YS3A, V2-S3, V2-YS3A
Internal current consumption
(5VDC)
0.3A
External
power supply
Voltage +15VDC/-15VDC
Current
consumption
+15VDC, 0.53A
-15VDC, 0.125A
Inrush current -
Weight 0.69kg

Table of Contents

Related product manuals