3  ANALOG OUTPUT MODULE REPLACEMENT
3 - 12
: Compatible, : Partial change required, ×: Incompatible
Q68DAVN Compatibility Precautions for replacement
16-bit signed binary
(Normal resolution mode: -4096 to 4095,
High resolution mode: -12288 to 12287, -16384 to 16383)
-10 to 10VDC (External load resistance value: 1k to 1M)
When using A616DAVN in [-5 to + 5V] 
range, Q68DAV can obtain equivalent 
resolution or more than A616DAV by 
setting in [-10 to 10V] range/ high 
resolution mode or user range. 
Ambient temperature 25±5°C: Within ±0.1% (±10mV) 
Ambient temperature 0 to 55°C: Within ±0.3% (±30mV)
-
80µs/channel
±12V
8 channels/module
Consider replacement with multiple 
Q68DAVN.
Max. 100,000 times
Available
Between the I/O terminal and programmable controller power supply: 
photocoupler isolation
Between output channels: non-isolation
Between external power supply and analog output: transformer isolation
Between the I/O terminal and programmable controller power supply: 
500VAC, for 1 minute
 Between the I/O terminal and programmable controller power supply: 
500VDC, 20M or more
16 points
(I/O assignment: intelligent 16 points)
The number of occupied I/O points 
has changed to 16 points.
18-point terminal block ×
Wiring change is required.
0.3 to 0.75mm
2
×
FG terminal: R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A
Terminals other than FG: R1.25-3
(Sleeved solderless terminal cannot be used.)
×
0.38A
Analog output
range
Normal resolution mode High resolution mode
Digital input 
value
Maximum 
resolution
Digital input 
value
Maximum 
resolution
Voltage
0 to 5V
0 to 4000
1.25mV
0 to 12000
0.416mV
1 to 5V 1.0mV 0.333mV
-10 to 10V
-4000 to 4000
2.5mV -16000 to 16000 0.625mV
User range 
settings
0.75mV -12000 to 12000 0.333mV