Appendix 1 Error Codes
727
A
2261H Parameter error
(network)
Different network types (CC IE
Control extended mode/normal
mode) are set between the control
station and the normal station.
Stop Check the detailed information
(parameter information) of the error by
executing module diagnostics using
the engineering tool and correct the
parameter setting corresponding to the
displayed number. If the same error
code is displayed again, the possible
cause is a hardware failure of the data
memory in the CPU module or the
intelligent function module connected.
Please consult your local Mitsubishi
representative.
Parameter
information
At power-on,
at RESET, at
STOP RUN
state
2262H Parameter error
(network)
Programmable controller CPU,
Safety CPU
When the station number of the
MELSECNET/H network module
is 0, parameters of PLC to PLC
network are set.
The station type set in the module
parameters differs from that of the
module actually mounted.
Process CPU, SIL2 Process CPU
When the station number of the
MELSECNET/H network module
is 0, parameters of PLC to PLC
network are set.
The station type set in the module
parameters differs from that of the
module actually mounted.
In the CPU module in redundant
mode, "RJ71GF11-T2" (the model
name cannot be set for the
redundant system) is selected to
the model name in the I/O
assignment setting of the system
parameter.
Stop Programmable controller CPU, Safety
CPU
Correct the station number of the
MELSECNET/H network module.
Check the detailed information
(parameter information) of the error by
executing module diagnostics using
the engineering tool and correct the
parameter setting corresponding to the
displayed number. If the same error
code is displayed again, the possible
cause is a hardware failure of the data
memory in the CPU module or the
intelligent function module connected.
Please consult your local Mitsubishi
representative.
Process CPU, SIL2 Process CPU
Correct the station number of the
MELSECNET/H network module.
Check the detailed information
(parameter information) of the error by
executing module diagnostics using
the engineering tool and correct the
parameter setting corresponding to the
displayed number.
In the CPU module in redundant mode,
select "RJ71GF11-T2(MR)",
"RJ71GF11-T2(SR)", or "RJ71GF11-
T2(LR)" (model names can be set for
the redundant system) to the model
name in the I/O assignment setting of
the system parameter.
If the same error code is displayed again,
the possible cause is a hardware failure
of the data memory in the CPU module or
the intelligent function module connected.
Please consult your local Mitsubishi
representative.
Parameter
information
At power-on,
at RESET, at
STOP RUN
state
2263H Parameter error
(network)
Even though the CC-Link IE
module or MELSECNET/H
network module is mounted, a
different CC-Link IE module or
MELSECNET/H network module
is set in the system parameters ("I/
O Assignment Setting"), or CC-
Link IE module or MELSECNET/H
network module parameters have
not been set.
Stop Set the system parameters and module
parameters. If the same error code is
displayed again, the possible cause is
a hardware failure of the data memory
in the CPU module or the intelligent
function module connected. Please
c
onsult your local Mitsubishi
representative.
Parameter
information
At power-on,
at RESET, at
STOP RUN
state
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing